Automatic FM 200 Cylinder

Automatic FM 200 Cylinder

Specification
  • Model NO: 180l
  • Cylinder Capacity: 180L
  • Storage Pressure: 2.5/4.2MPa
  • Cylinder Color: Red
  • Operating Method: Electromagnetic Starter; Emergency Mechanical Star
  • Transport Package: Wooden Case
  • Specification: 40L/70L/100L/120L/150L/180L
  • Trademark: WELFARE
  • Origin: China (Mainland)
  • HS Code: 842410000
  • Production Capacity: 20000bottle /Set Per Month

Product Description

Automatic FM 200 Cylinder
1. Automatic fire fighting System Introduction:

HFC-227ea is a clean extinguishing agent, which would completely vaporized in the air, and well
Insulated. Its total flooding mode is applicable to electric fire, liquid fire or fusible solid fire, solid
Surface fire, gas fire which gas supply is cut before extinguishing. And it is able to protect computer
Rooms, communication rooms, substation rooms, hi-tech device rooms, generator rooms, gasoline
Storerooms, combustible chemical storerooms, libraries, data rooms, archives, treasuries, etc. We
Manufacture HFC-227ea system that is well structured, reliable, and widely applied to computer
Rooms, archives, program control exchange engine rooms, TV broadcast center, financial
Organizations and government departments.

2 180l FM200 fire suppression System Main Technical Parameter:

1.2.1  Storage of cylinder: 180L
1.2.2  20ºC Storage Pressure: 4.2MPa.
1.2.3  Maximum Working Pressure(50ºC): 6.7MPa
1.2.4  Operating Method: electromagnetic starter; emergency mechanical starter
1.2.5  Electromagnetic driving device:Nitrogen pressure 6.0±1.0MPa(20ºC),Starter power: DC24V/1.5A
1.2.6  Extinguishing agent filling density:  ≤950kg/m3(4.2MPa)
1.2.7  Extinguishing agent spurting time:  ≤8s.
1.2.8  Protective Area Temperature:  -10ºC~50ºC.
1.2.9  Cylinder spurting allowance:: ≤2Kg/bottle.
1.2.10 Cylinder-room temperature requirement: -10ºC~50ºC.